Construction & selection
Single-core copper cables with XLPE insulation and aluminium-wire armour. The illustrated construction uses PVC bedding and an outer PVC sheath; other sheath compounds require configuration-specific confirmation.
For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Construction
Illustrated variant: CU/XLPE/PVC/AWA/PVC
- Copper conductor
The copper conductor forms the current-carrying element of the cable.
- XLPE insulation
Cross-linked polyethylene forms the main electrical insulation around the conductor.
- PVC bedding
PVC forms a bedding layer between the insulated core assembly and the armour.
- Aluminium wire armour
Aluminium wires form the mechanical armour around the cable.
- PVC outer sheath
PVC forms the external protective covering around the cable assembly.
The illustrated variant uses PVC bedding and a PVC outer sheath; the LSZH alternative is not shown.
Construction source: supplier LV reference catalogue, page 10.
Family reference
| Illustrated conductor | Copper |
|---|---|
| Illustrated configuration | CU/XLPE/PVC/AWA/PVC |
| Construction layers | stranded copper; XLPE insulation; PVC bedding; aluminium wire armour; PVC outer sheath |
| Reference voltage family | 600/1000 V catalogue family; confirm the selected current datasheet |
| Selection requirement | Confirm size, rated voltage, installation conditions and applicable standards before ordering |
Technical specifications
Single-core copper XLPE/AWA
- Rated voltage
- 600/1000 V
- Construction
- CU/XLPE/PVC(LSZH)/AWA/PVC(LSZH), source sheath alternatives retained
- Standards — catalogue-stated
- IEC 60502-1 (supplier catalogue statement; edition not stated).
Reference catalogue data for the selected construction, not certification or a guarantee of current availability. Confirm the current datasheet before ordering.
| Nominal conductor area (mm²) | Maximum conductor resistance at 20°C (Ω/km) | Insulation thickness (mm) | Extruded bedding thickness (mm) | Armour wire diameter (mm) | Outer sheath thickness (mm) | Approximate overall diameter (mm) | Approximate cable weight (kg/km) |
|---|---|---|---|---|---|---|---|
| 50 | 0.387 | 1.0 | 1.0 | 1.25 | 1.8 | 19.1 | 775 |
| 70 | 0.268 | 1.1 | 1.0 | 1.25 | 1.8 | 20.9 | 1000 |
| 95 | 0.193 | 1.1 | 1.0 | 1.25 | 1.8 | 22.7 | 1300 |
| 120 | 0.153 | 1.2 | 1.0 | 1.6 | 1.8 | 25.2 | 1620 |
| 150 | 0.124 | 1.4 | 1.0 | 1.6 | 1.8 | 27.0 | 1940 |
| 185 | 0.0991 | 1.6 | 1.0 | 1.6 | 1.8 | 29.0 | 2300 |
| 240 | 0.0754 | 1.7 | 1.0 | 1.6 | 1.9 | 31.9 | 2910 |
| 300 | 0.0601 | 1.8 | 1.0 | 1.6 | 1.9 | 34.1 | 3530 |
| 400 | 0.0470 | 2.0 | 1.2 | 2.0 | 2.1 | 39.0 | 4610 |
| 500 | 0.0366 | 2.2 | 1.2 | 2.0 | 2.2 | 42.6 | 5690 |
| 630 | 0.0283 | 2.4 | 1.2 | 2.0 | 2.2 | 47.0 | 7150 |
| 800 | 0.0221 | 2.6 | 1.4 | 2.5 | 2.5 | 55.5 | 9200 |
| 1000 | 0.0176 | 2.8 | 1.4 | 2.5 | 2.5 | 61.2 | 11580 |
- Circular stranded or circular stranded compacted Class 2; natural insulation colour.
- PVC and LSZH are alternative compounds, not interchangeable certifications.
Source: supplier LV reference catalogue, PDF page 10 (printed 7). Approximate values are identified in column headings. Asterisks retain source conductor variants.
Project-specific confirmation
Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.