Three-Core Copper Power Cables

Back to cable catalogue
LV · Cable family

Construction & selection

Three-core copper power-cable family with PVC and XLPE variants. The illustration shows an unarmoured PVC-insulated, PVC-sheathed configuration; insulation and armour must be selected for the installation.

For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Representative illustration: Three-Core Copper Power Cables
Representative illustration of one configuration. Actual construction, colour and dimensions depend on the selected specification.

Construction

Illustrated variant: CU/PVC/PVC unarmoured

Representative construction of CU/PVC/PVC unarmoured, with numbered components 1 to 4, explained below.
Representative construction of the selected variant; not to scale. Strand counts, colours and dimensions are illustrative.
  1. Copper conductors

    The copper conductors form the current-carrying elements of the insulated cores.

  2. PVC insulation

    PVC provides the electrical insulation around each conductor.

  3. Core assembly and fillers

    The insulated cores are assembled together, with fillers occupying the spaces between them.

  4. PVC outer sheath

    PVC forms the external protective covering around the cable assembly.

Construction source: supplier LV reference catalogue, page 21.

Family reference

Illustrated conductorCopper
Illustrated configurationCU/PVC/PVC unarmoured circular stranded option
Construction layersthree stranded copper cores; individual PVC insulation; filler; common PVC sheath
Reference voltage family600/1000 V catalogue family; confirm the selected current datasheet
Selection requirementConfirm size, rated voltage, installation conditions and applicable standards before ordering

Technical specifications

Three-core copper PVC/PVC — unarmoured

Rated voltage
600/1000 V
Construction
Three copper cores; PVC insulation and PVC sheath
Standards — catalogue-stated
10–400 mm² generally BS 6346; 500 mm² IEC 60502-1. This page does not state a standard for smaller sizes.

Reference catalogue data for the selected construction, not certification or a guarantee of current availability. Confirm the current datasheet before ordering.

Nominal conductor area (mm²)Maximum conductor resistance at 20°C (Ω/km)Insulation thickness (mm)Outer sheath thickness (mm)Approximate overall diameter (mm)Approximate cable weight (kg/km)
1.5*12.10.81.811.5180
1.512.10.81.811.9190
2.5*7.410.81.812.4225
2.57.410.81.812.8235
44.611.01.814.8330
63.081.01.816.0410
101.831.01.818.2560
161.151.01.820.4775
250.7271.21.821.21050
350.5241.21.823.51360
500.3871.41.827.11760
700.2681.42.029.72390
950.1931.62.134.53240
1200.1531.62.237.73990
1500.1241.82.340.44900
1850.09912.02.545.16040
2400.07542.22.751.67820
3000.06012.42.856.19660
4000.04702.63.163.712410
5000.03662.83.469.115480
  • * denotes circular solid Class 1. Other conductors through 16 mm² are circular stranded Class 2; 25 mm² and larger are shaped stranded Class 2.
  • PVC compound alternatives are Type 5 heat-resisting 85°C with Type 9/ST2 sheath, or Type A/TI1 with ST1/TM1 sheath. This is not a universal operating-temperature rating.

Source: supplier LV reference catalogue, PDF page 21 (printed 18). Approximate values are identified in column headings. Asterisks retain source conductor variants.

Project-specific confirmation

Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.

Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.