Construction & selection
Bare stranded hard-drawn copper conductor family for overhead applications. The illustration represents bare copper construction; conductor size and mechanical performance require selection from the current datasheet.
For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Construction
Illustrated variant: HDBC bare copper
- Hard-drawn copper strands
Hard-drawn copper strands make up the bare current-carrying conductor.
- Bare stranded conductor assembly
The strands are laid together as a bare conductor, without insulation or an outer sheath.
Construction source: supplier overhead conductor reference catalogue, page 8.
Family reference
| Illustrated conductor | Copper |
|---|---|
| Illustrated configuration | Hard-drawn bare copper stranded conductor |
| Construction layers | stranded copper only |
| Selection requirement | Confirm size, rated voltage, installation conditions and applicable standards before ordering |
Engineering data
Manufacturer catalogue reference: PDF page 8 (printed page 4).
BS 7884-1997 (catalogue statement)
| Nominal area (mm²) | Number of wires (No.) | Nominal wire diameter (mm) | Approx. conductor diameter (mm) | Maximum resistance at 20°C (Ω/km) | Nominal weight (kg/km) | Maximum weight (kg/km) | Minimum breaking load (N) |
|---|---|---|---|---|---|---|---|
| 10 | 7 | 1.35 | 4.05 | 1.829 | 89.82 | 91.62 | 3752 |
| 14 | 7 | 1.60 | 4.80 | 1.303 | 126.2 | 128.7 | 5267 |
| 16 | 3 | 2.65 | 5.70 | 1.106 | 148.3 | 151.3 | 6194 |
| 16 | 7 | 1.70 | 5.10 | 1.154 | 142.4 | 145.2 | 5946 |
| 25 | 7 | 2.10 | 6.30 | 0.7563 | 217.3 | 221.6 | 9073 |
| 32 | Not specified | 3.75 | 8.06 | 0.552 | 296.9 | 302.8 | 12400 |
| 32 | 7 | 2.46 | 7.38 | 0.5497 | 298.2 | 304.2 | 12442 |
| 35 | 7 | 2.5 | 7.50 | 0.5337 | 308 | 314.2 | 12860 |
| 50 | 7 | 3.00 | 9.00 | 0.3706 | 443.5 | 452.4 | 18520 |
| 50 | 19 | 1.80 | 9.00 | 0.3819 | 435.8 | 444.5 | 17700 |
| 70 | 7 | 3.55 | 10.65 | 0.2646 | 621.1 | 633.5 | 25930 |
| 70 | 19 | 2.10 | 10.5 | 0.2806 | 593.2 | 605.1 | 24090 |
| 95 | 19 | 2.50 | 12.5 | 0.198 | 840.7 | 857.5 | 34140 |
| 100 | 7 | 4.30 | 12.9 | 0.181 | 911.2 | 929.4 | 36540 |
| 120 | 19 | 2.80 | 14.00 | 0.1578 | 1055 | 1076 | 42830 |
| 150 | 19 | 3.20 | 16.00 | 0.1208 | 1377 | 1405 | 55940 |
| 150 | 37 | 2.25 | 15.75 | 0.1264 | 1334 | 1361 | 53880 |
| 185 | 19 | 3.55 | 17.75 | 0.09815 | 1695 | 1729 | 68860 |
| 185 | 37 | 2.5 | 17.5 | 0.1024 | 1647 | 1680 | 66490 |
- The 32 mm² / 3.75 mm row has an unresolved source wire-count inconsistency; the wire count is not specified here.
- Values are transcribed from the supplied manufacturer catalogue, not independently certified test results. Final construction, applicable standard edition and project suitability require technical review.
Project-specific confirmation
Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.
Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.