Soft-drawn bare copper earthing conductors (SDBC)

Back to cable catalogue
OVERHEAD · Cable family

Construction & selection

Soft-drawn bare copper earthing-conductor family. The illustration shows an untinned stranded copper option. Size, termination method and installation suitability require project-specific selection.

For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Representative illustration: Soft-drawn bare copper earthing conductors (SDBC)
Representative illustration of one configuration. Actual construction, colour and dimensions depend on the selected specification.

Construction

Illustrated variant: SDBC untinned bare copper

Representative construction of SDBC untinned bare copper, with numbered components 1 to 2, explained below.
Representative construction of the selected variant; not to scale. Strand counts, colours and dimensions are illustrative.
  1. Soft-drawn copper strands

    Soft-drawn copper strands make up the bare current-carrying conductor.

  2. Bare stranded conductor assembly

    The strands are laid together as a bare conductor, without insulation or an outer sheath.

Construction source: supplier overhead conductor reference catalogue, page 25.

Family reference

Illustrated conductorCopper
Illustrated configurationUntinned soft-drawn stranded copper earthing conductor
Construction layersuntinned copper strands only
Selection requirementConfirm size, rated voltage, installation conditions and applicable standards before ordering

Engineering data

Manufacturer catalogue reference: PDF page 25 (printed page 21).

BS 6360 / BS EN 60228 and IEC 60228 (catalogue statement)

Soft-drawn bare copper earthing conductor (SDBC) — catalogue reference values
Nominal area (mm²)Minimum number of wires (No.)Approx. conductor diameter (mm)Maximum resistance at 20°C (Ω/km)Approx. conductor weight (kg/km)
472.524.6134.0
673.083.0851.0
1073.81.8387.0
1664.91.15136
2566.00.727215
3567.10.524301
5068.20.387410
70129.80.268594
951511.70.193820
1201813.20.1531040
1501814.60.1241300
1853016.20.09911615
2403418.70.07542100
3003420.70.06012650
4005323.60.0473440
  • Source describes Class 2 circular-stranded/compacted conductors; exact construction is subject to the selected item. Non-compacted untinned or tinned variants are stated as available on request.
  • Values are transcribed from the supplied manufacturer catalogue, not independently certified test results. Final construction, applicable standard edition and project suitability require technical review.

Project-specific confirmation

Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.

Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.