LV · Cable family

Construction & selection

Four-core copper cables with three phase conductors and a smaller neutral conductor. The illustrated option uses PVC insulation and a common PVC sheath without armour; the neutral size must be confirmed for the application.

For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Representative illustration: Reduced-Neutral Copper Power Cables
Representative illustration of one configuration. Actual construction, colour and dimensions depend on the selected specification.

Construction

Illustrated variant: CU/PVC/PVC with reduced neutral

Representative construction of CU/PVC/PVC with reduced neutral, with numbered components 1 to 5, explained below.
Representative construction of the selected variant; not to scale. Strand counts, colours and dimensions are illustrative.
  1. Three larger copper phase conductors

    Three larger copper conductors form the phase elements of the selected reduced-neutral construction.

  2. Smaller copper neutral conductor

    The smaller copper conductor forms the neutral element of the selected construction.

  3. PVC insulation

    PVC provides the electrical insulation around each conductor.

  4. Core assembly and fillers

    The insulated cores are assembled together, with fillers occupying the spaces between them.

  5. PVC outer sheath

    PVC forms the external protective covering around the cable assembly.

Construction source: supplier LV reference catalogue, page 35.

Family reference

Illustrated conductorCopper
Illustrated configurationCU/PVC/PVC four-core reduced neutral, circular stranded small-size option
Construction layersthree larger stranded copper cores and one smaller neutral copper core; individual PVC insulation; filler; common PVC sheath
Reference voltage family600/1000 V catalogue family; confirm the selected current datasheet
Selection requirementConfirm size, rated voltage, installation conditions and applicable standards before ordering

Technical specifications

Four-core copper PVC with reduced neutral

Rated voltage
600/1000 V
Construction
Three phase conductors and reduced neutral; CU/PVC/PVC
Standards — catalogue-stated
The page states “*Cables conform to IEC 60502-1”; the asterisk also marks the 10 and 16 mm² phase rows. Applicability to unstarred rows requires confirmation.

Reference catalogue data for the selected construction, not certification or a guarantee of current availability. Confirm the current datasheet before ordering.

Phase conductor area (mm²)Neutral conductor area (mm²)Phase maximum resistance at 20°C (Ω/km)Neutral maximum resistance at 20°C (Ω/km)Phase insulation thickness (mm)Neutral insulation thickness (mm)Outer sheath thickness (mm)Approximate overall diameter (mm)Approximate cable weight (kg/km)
10*61.833.081.01.01.818.2540
16*101.151.831.01.01.820.7760
25160.7271.151.21.01.823.31140
35160.5241.151.21.01.826.71450
50250.3870.7271.41.21.930.31970
70350.2680.5241.41.22.033.42690
95500.1930.3871.61.42.238.83670
120700.1530.2681.61.42.341.74590
150700.1240.2681.81.42.446.65560
185950.09910.1932.01.62.651.56940
2401200.07540.1532.21.62.857.18860
3001500.06010.1242.41.83.063.111080
3001850.0601Not stated / withheld2.42.03.063.311370
4001850.04700.09912.62.03.270.514110
5002400.03660.07542.82.23.578.718300
  • Phase conductors through 16 mm² circular stranded Class 2; 25 mm² and larger shaped stranded Class 2. Neutral conductors circular stranded Class 2.
  • PVC compound alternatives are Type 5 heat-resisting 85°C with Type 9/ST2 sheath, or Type A/TI1 with ST1/TM1 sheath. This is not a universal operating-temperature rating.
  • One or more entries in neutral resistance are withheld pending source confirmation; unaffected values remain available.

Source: supplier LV reference catalogue, PDF page 35 (printed 32). Approximate values are identified in column headings. Asterisks retain source conductor variants.

Project-specific confirmation

Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.

Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.