Triplex service drop cable

Back to cable catalogue
OVERHEAD · Cable family

Construction & selection

Triplex service-drop cable configurations. The illustrated selection has two insulated aluminium phase conductors twisted with one bare AAC aluminium messenger, without a common sheath. Application and messenger construction require confirmation.

For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Representative illustration: Triplex service drop cable
Representative illustration of one configuration. Actual construction, colour and dimensions depend on the selected specification.

Construction

Illustrated variant: XLPE insulated aluminium phases + bare AAC messenger

Representative construction of XLPE insulated aluminium phases + bare AAC messenger, with numbered components 1 to 4, explained below.
Representative construction of the selected variant; not to scale. Strand counts, colours and dimensions are illustrative.
  1. Aluminium phase conductors

    The aluminium conductors form the current-carrying elements of the insulated phases.

  2. XLPE phase insulation

    XLPE provides individual electrical insulation around each aluminium phase conductor.

  3. Bare AAC aluminium messenger

    The bare AAC aluminium messenger supports the twisted assembly alongside the insulated phase conductors.

  4. Twisted service-drop assembly

    The selected assembly combines two insulated phase conductors with one bare AAC aluminium messenger.

The image shows two XLPE-insulated aluminium phase conductors and one bare AAC aluminium messenger. PE insulation, AAAC and ACSR alternatives are not illustrated.

Construction source: supplier overhead conductor reference catalogue, page 32.

Family reference

Illustrated conductorAluminium
Illustrated configurationXLPE-insulated aluminium phases with bare AAC messenger
Construction layers2 separately XLPE-insulated aluminium phase conductor(s); one bare stranded aluminium AAC messenger; twisted together; NO common sheath
Selection requirementConfirm size, rated voltage, installation conditions and applicable standards before ordering

Engineering data

Manufacturer catalogue reference: PDF page 32 (printed page 28).

Source p.31: 600 V or lower; 600 V marking.

PDF p.31 lists B-230, B-231, B-232, B-399, B-339 and B-498. Its ANSI/ICEA S-76-474 sentence says Duplex, not Triplex; no verified Triplex compliance claim is made.

Triplex service-drop cable — catalogue reference values
Code wordMessenger groupPhase size / wire count (source designation)Insulation thickness (mm)Nominal bare phase diameter (mm)Nominal insulated phase diameter (mm)Bare neutral size / wires (source designation)Rated strength (source unit) (kg)Nominal total weight (kg/km)Catalogue ampacity (A)
HalotisAAC6-Solid1.144.1156.46-725515278
PikeAAC6-70.764.676.26-725514378
PatellaAAC6-71.144.677.06-725515978
AlbusAAC6-71.524.677.76-725519878
FususAAC4-Solid1.145.1827.54-7400229103
OysterAAC4-71.145.898.24-7400237103
ArgoAAC4-71.525.898.94-7400258103
ClamAAC2-71.147.429.72-7612359136
ThiaAAC2-71.527.4210.52-7612383136
MusselAAC2-71.147.429.72-7612359136
PyrulaAAC1-71.528.3311.41-7744467158
HyasAAC1-191.528.4311.51-7744469158
MurexAAC1/0-71.529.3512.41/0-7903513182
PurpuraAAC1/0-191.529.4712.51/0-7903515182
NasaAAC2/0-71.5210.5213.62/0-71,139710210
TrophonAAC2/0-191.5210.6413.72/0-71,139713210
QuahogAAC3/0-72.0311.7915.93/0-71,379926242
LoneAAC3/0-192.0311.9416.03/0-71,379929242
MelitaAAC3/0-191.5211.9415.03/0-191,501881242
CoquilaAAC4/0-71.5213.2616.34/0-71,7371,089279
TuskAAC4/0-72.0313.2617.34/0-71,7371,141279
ApusAAC4/0-192.0313.4117.54/0-71,7371,144279
PortunusAAC4/0-191.5213.4116.54/0-191,8231,091279
ChitonAAC266.8-192.0314.8818.9266.8-192,2541,409310
NannynoseAACNot specified2.0316.9221.0336.4-192,7901,749330
  • Source p.31 contains copied Duplex wording and a B-339/B-399 inconsistency. Applicable standards require manufacturer clarification.
  • Rated strength retains source kg label; no kgf/kN conversion. Size designations retain their source form without inferred units.
  • Ampacity is a catalogue reference only; confirm design conditions.
  • The Nannynose phase designation has an unresolved source inconsistency and is withheld pending manufacturer confirmation.
  • Values are transcribed from the supplied manufacturer catalogue, not independently certified test results. Final construction, applicable standard edition and project suitability require technical review.

Project-specific confirmation

Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.

Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.