HAISHAN INDUSTRY · GLOBAL PROJECT SOLUTIONS

Quadruplex service drop cable

Back to cable catalogue
OVERHEAD · Cable family

Construction & selection

Quadruplex service-drop cable configurations. The illustrated selection has three insulated aluminium phase conductors twisted with one bare AAC aluminium messenger, without a common sheath. Current ratings and installation conditions are configuration-specific.

For technical data and a quotation, use Contact in the main navigation and include this cable family in your enquiry.

Representative illustration: Quadruplex service drop cable
Representative illustration of one configuration. Actual construction, colour and dimensions depend on the selected specification.

Construction

Illustrated variant: XLPE insulated aluminium phases + bare AAC messenger

Representative construction of XLPE insulated aluminium phases + bare AAC messenger, with numbered components 1 to 4, explained below.
Representative construction of the selected variant; not to scale. Strand counts, colours and dimensions are illustrative.
  1. Aluminium phase conductors

    The aluminium conductors form the current-carrying elements of the insulated phases.

  2. XLPE phase insulation

    XLPE provides individual electrical insulation around each aluminium phase conductor.

  3. Bare AAC aluminium messenger

    The bare AAC aluminium messenger supports the twisted assembly alongside the insulated phase conductors.

  4. Twisted service-drop assembly

    The selected assembly combines three insulated phase conductors with one bare AAC aluminium messenger.

The image shows three XLPE-insulated aluminium phase conductors and one bare AAC aluminium messenger. PE insulation, AAAC and ACSR alternatives are not illustrated.

Construction source: supplier overhead conductor reference catalogue, page 38.

Family reference

Illustrated conductorAluminium
Illustrated configurationXLPE-insulated aluminium phases with bare AAC messenger
Construction layers3 separately XLPE-insulated aluminium phase conductor(s); one bare stranded aluminium AAC messenger; twisted together; NO common sheath
Selection requirementConfirm size, rated voltage, installation conditions and applicable standards before ordering

Engineering data

Manufacturer catalogue reference: PDF page 38 (printed page 34).

Source p.37:600 V or lower;600 V marking.

PDF p.37 lists B-230, B-231, B-232, B-399, B-339 and B-498. Its ANSI/ICEA S-76-474 sentence says Duplex, not Quadruplex; no verified Quadruplex compliance claim is made.

Quadruplex service-drop cable — catalogue reference values
Code wordMessenger groupPhase size / wire count (source designation)Insulation thickness (mm)Nominal bare phase diameter (mm)Nominal insulated phase diameter (mm)Bare neutral size / wires (source designation)Rated strength (source unit) (kg)Nominal total weight (kg/km)Catalogue ampacity (A)
QuarterAAC6-Solid1.1434.1156.4016-7255.37121178
ClydesdaleAAC4-Solid1.1435.1827.4684-7399.613315103
PintoAAC4-71.1435.8938.1794-7399.613326136
MusangAAC2-71.1437.4179.7032-7612.347491158
ShireAAC1-191.5248.43311.4811-19743.888646158
PercheronAAC2/0-191.52410.64313.6912/0-191138.511976210
MongolianAAC3/0-71.52411.78614.8343/0-71378.9141199242
HanoverianAAC3/0-191.52411.93814.9863/0-191378.9141204242
SinglefootAAC4/0-71.52413.25916.3074/0-71737.2501485279
OldenburgAAC4/0-191.52413.41116.4594/0-191737.2501490279
  • Source conditions:40°C ambient,90°C conductor temperature,sun and wind. Values approximate and subject to normal manufacturing tolerances.
  • Source p.37 has copied Duplex wording and B-339/B-399 inconsistency; standards require confirmation.
  • Rated strength retains source kg label without interpreting kgf; phase/neutral designation units not inferred.
  • Values are transcribed from the supplied manufacturer catalogue, not independently certified test results. Final construction, applicable standard edition and project suitability require technical review.

Project-specific confirmation

Confirm the required conductor material, core arrangement, voltage designation, installation conditions, size and applicable standards with your enquiry. Reference tables on this page give data for the stated construction; confirm the selected current datasheet before ordering.

Illustrations are not engineering drawings or factory photographs. Final specifications and approved drawings will be confirmed with our official quotation. No certification or current manufacturer availability is implied by this family overview.